Toggle navigation
|
Inbox
View Profile
Log Out
FM.MT.05.01
SURAT PERINTAH KERJA ( WORK ORDER )
WORKORDERNO
WORKCENTER
PRIORITY
TGLDIKERJAKAN
DURASIPEKERJAAN
EQUIPNO
JUMLAHORANG
EQUIPDESC
DESKRIPSI KERJA
PENGECEKAN PARAMETER MAKEUP WATER & COOLING WATER
MATERIAL
TOOLS
Alkalinity test kitz (1), Chloride testr kitz (1), Hardness test kitz (1)
Multi parameter water quality monitor (1), Gelas beaker 500 ml (1)
PROCEDURE :
Safety : 1. Gunakan APD chemical handling Environment : Buang air hasil pengetesan ke bak limbah Langkah kerja : 1. Gunakan sarung tangan latex 2. Siapkan sampling makeup water(industrial water) & cooling water minimal 250 ml 3. Siapkan alat pengetesan parameter 4. Tes pH meter, TDS & turbidity 5. Pengetesan titrasi : - P alkalinity -M alkalinity -Total hardness -Chloride 6. 5S
TglMulai
TglSelesai
TotalJam
Status
NamaPekerja1
NamaPekerja3
NamaPekerja2
NamaPekerja4
Comment :
Total chlorine Senin : 0.07 NTU Selasa : 0.76 NTU Rabu : 0.96 NTU kamis : 0.05 NTU Jumat : 6.86 NTU
7c17082c-65b6-463c-a980-397f2e983ff7.jpg
Download
Back to List