Toggle navigation
|
Inbox
View Profile
Log Out
FM.MT.05.01
SURAT PERINTAH KERJA ( WORK ORDER )
WORKORDERNO
WORKCENTER
PRIORITY
TGLDIKERJAKAN
DURASIPEKERJAAN
EQUIPNO
JUMLAHORANG
EQUIPDESC
DESKRIPSI KERJA
PENGECEKAN PARAMETER MAKEUP WATER & COOLING WATER
MATERIAL
TOOLS
Multi parameter water quality monitor (1)
PROCEDURE :
Safety : 1. Gunakan APD chemical handling Environment : Buang air hasil pengetesan ke bak limbah Langkah kerja : 1. Gunakan sarung tangan latex 2. Siapkan sampling makeup water(industrial water) & cooling water minimal 250 ml 3. Siapkan alat pengetesan parameter 4. Tes pH meter, TDS & turbidity 5. Pengetesan titrasi : - P alkalinity -M alkalinity -Total hardness -Chloride 6. 5S
TglMulai
TglSelesai
TotalJam
Status
NamaPekerja1
NamaPekerja3
NamaPekerja2
NamaPekerja4
Comment :
*Makeup water P Alkalinity = 0 ppm M alkalinity = 20 ppm Hardness = 33 ppm Cloride = 40 ppm pH = 6.27 TDS = 60 Turbidity = 0.32 NTU *Cooling water P Alkalinity = 0 ppm M alkalinity = 80 ppm Hardness = 235 ppm Cloride = 190 ppm pH = 8.22 TDS = 500 Turbidity = 27.78 NTU
1000257549.pdf
Download
Back to List