PENGECEKAN PARAMETER MAKEUP WATER & COOLING WATER
MATERIAL
TOOLS
ABC Alkalinity ABC Hardness ABC Chloride
Multi parameter water quality monitor
PROCEDURE :
Safety : 1. Gunakan APD chemical handling Environment : Buang air hasil pengetesan ke bak limbah Langkah kerja : 1. Gunakan sarung tangan latex 2. Siapkan sampling makeup water(industrial water) & cooling water minimal 250 ml 3. Siapkan alat pengetesan parameter 4. Tes pH meter, TDS & turbidity 5. Pengetesan titrasi : - P alkalinity -M alkalinity -Total hardness -Chloride 6. 5S
TglMulai
TglSelesai
TotalJam
Status
NamaPekerja1
NamaPekerja3
NamaPekerja2
NamaPekerja4
Comment :
Senin: 6.2 (Little scale or corrosion) Selasa : 5.6.(Light scale) Rabu : 6.1 (Little scale or corrosion) Kamis : 5.7 (Light scale) Jumat : 6.1 (Little scale or corrosion)